Macroair Fault Codes
Question: 1000
Answer: (High voltage warning )
Incoming voltages are suspected to be high.
Check voltages and make sure their not too high
Question: 1001
Answer: (Low voltage warning)
Incoming voltages are suspected to be low.
Check voltages and make sure their not low.
Question: 1002
Answer: (High voltage fault)
Power issue
Perform power cycle
Reset the breaker. And wait 90 secs to turn fan on
Check incoming voltages on L1 , L2 if single phase.
Check L1 , L2 and L3
Question: 1004
Answer: (Phase current A high)
Current not regulating,vibration or sudden shutdown.
Verify motor parameters, perform power calibration, possible bad drive.
Question: 1005
Answer: (Phase current B high)
Current not regulating, vibration or sudden shutdown.
Verify motor parameters, perform power calibration, possible bad drive.
Question: 1006
Answer: (Phase current high C)
Current not regulating, vibration or sudden shutdown. verify motor parameters, perform power calibration, possible bad drive.
Question: 1013
Answer: (Phase current following error)
Fan stops
Verify blade settings
Verify motor parameters
Fine tuning lower rpms
Verify number of blades. Maintain clearance from blades to structure
Question: 1014
Answer: (Sudden change of fam speed) controller looks for a change in speed bounded by a minimum RPM in a certain amount of time. 10 (20%) rpms in 0.1 sec
NO obstructions in blades perform power calibration verify motor parameters
Question: 1015
Answer: (Tilt limit exceeded)
Fan is vibration more than normal.
Verify mount is secure and bolts are tightened appropriately. Make sure guy wires are tight no slack on them.
Question: 1016
Answer: (Vibration limit exceeded)
(Tilt limit exceeded)
Fan is vibration more than normal.
Verify mount is secure and bolts are tightened appropriately. Make sure guy wires are tight no slack on them.